Commissioning
4.8 Acceptance test - Completion of commissioning
Table 4- 3
Example:
Drive
1
2
4.8.5

Function test

4.8.5.1

Safe Torque Off, STO (Basic Safety)

The following is checked during the function test:
● The hardware is functioning properly.
● The digital inputs of the inverter are assigned correctly for the safety function.
● The PROFIsafe address of the inverter is set correctly.
● The safety function is parameterized correctly.
● Routine for forced dormant error detection of the switch-off signal paths on the Control
Note
Perform the acceptance test with the maximum possible speed and acceleration.
Procedure
Table 4- 4
"Safe Torque Off" (STO) function
No.
1.
Initial state:
The inverter is in "Ready" state (p0010 = 0).
The inverter indicates neither faults nor alarms for safety functions (r0945, r2122, r2132).
STO is not active.
2.
Switch on the motor (ON command).
3.
Ensure that the correct motor is running.
4.
Select STO while the motor is running
Note: Test each configured activation, e.g. via digital inputs and PROFIsafe.
120
Safety function
STO
SS1
SS1
SLS 0
SLS 2
Unit.
Limit
-
Reference speed = 1500 rpm
Delay time = 250 ms
Monitoring time = 5 s
Reference speed = 1500 rpm
Delay time = 250 ms
Monitoring time = 8 s
150 rpm
1500 rpm
Description
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
Safety Integrated Function Manual, SINAMICS G120