6.4

List of faults

The following table lists all faults for the safety functions. The complete list of all faults for the
inverter can be found in the List Manual.
Fault
F01600
F01611
F01620
F01625
F01649
F01650
F01651
F01653
F01656
F01659
F01665
F01666
F01680
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
Cause
Further information can be found in the online help of STARTER and the List
Manual.
STOP A triggered.
More detailed information is provided by
fault value r0949.
Defect in a monitoring channel.
More detailed information is supplied by
fault value r0949.
Safe Torque Off active.
Sign-of-life error in the safety data.
Internal software error
Acceptance test required
Synchronization, safety time slices
unsuccessful.
PROFIBUS configuration error
Motor Module parameter error.
Write request for parameter rejected.
System is defective.
Static 1 signal at the F-DI for safe
acknowledgement.
Checksum error safe monitoring
functions.
Alarms, faults and system messages
6.4 List of faults
Remedy
Activate and then deactivate STO.
Replace the CU if the fault cannot be
acknowledged.
Check the F-DI wiring and set the signal
filter (discrepancy, contact bounce, or bit
pattern test). Switch the Control Unit
power supply off and then on again if the
fault cannot be acknowledged.
Replace the CU if the fault cannot be
acknowledged.
Depends on the triggering message.
Activate and then deactivate STO.
Replace the CU if the fault cannot be
acknowledged.
Switch the Control Unit power supply off
and then on again.
Replace the CU if the fault cannot be
acknowledged.
Perform a functions test, create an
acceptance report and acknowledge the
fault.
Switch the Control Unit power supply off
and then on again.
Replace the CU if the fault cannot be
acknowledged.
Check the PROFIBUS configuration of
the safety slot on the master side and on
the Control Unit, and correct if
necessary.
Recommission the safety functions.
If unsuccessful, replace the CU.
Check the following:
- Password
- Reset to the factory setting only when
the safety functions have been disabled.
Switch the Control Unit power supply off
and then on again.
Replace the CU if the fault cannot be
acknowledged.
Set the F-DI for acknowledging the
safety function to logical 0 signal.
Check the safety-relevant parameters.
Switch the Control Unit power supply off
and then on again.