4.3.3.3

Activate settings

● Click "Copy parameters" and then click "Activate settings":
● If the password = 0 (factory setting), follow the prompts in order to set a password.
● Confirm the prompt for saving your settings (copy RAM to ROM).
● Switch off the Control Unit power supply for approximately 10 seconds (Power ON
When you connect the inverter to the central controller via the fieldbus for the first time, the
central controller sends the PROFIsafe configuration to the inverter. Once the configuration
data has been received, the inverter interconnects its internal signals with the PROFIsafe
telegram.
Note
Monitoring PROFIsafe communication
The inverter monitors communication with the central controller. The inverter does not start
monitoring communication until the configuration data has been received from the central
controller.
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 40).
Reset). Only then will your changes become effective.
Commissioning
4.3 Basic Safety