4.3.3

Activating STO via PROFIsafe and F-DI

Procedure
● Go online with STARTER.
● In STARTER, call up the screens displaying the fail-safe functions and click on "Change
4.3.3.1

Defining the commissioning method

Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
settings":
Set "STO via PROFIsafe and Terminal".
If you require the status signal "STO active" in your higher-level controller,
interconnect it accordingly.
Enter the same PROFIsafe address as a hexadecimal value that you defined in the
hardware configuration, see Section Configuring communication in STEP 7 (telegram 30)
(Page 64).
Click the button to set the STO.
Commissioning
4.3 Basic Safety
79