Commissioning
4.4 Extended Safety
4.4.2.8
Parameterizing SLS
● Set the following in this screen:
● Close the screen.
4.4.2.9
Defining the F-DI status
If you do not want to transfer the status of the fail-safe inputs via PROFIsafe, go straight to
the section Activate settings (Page 101).
If you want to transfer the status of the fail-safe digital inputs via PROFIsafe, you first have to
configure the relevant PROFIsafe telegram; see the section Configuring communication in
STEP 7 (telegram 900) (Page 66). In STARTER, you then have to specify which F-DI-Status
you want to transfer via PROFIsafe.
100
①
–
Setpoint speed limit as a % of the monitoring threshold.
This parameter defines the upper speed limit when SLS is active.
②
–
Monitoring threshold
Enter the load-side speed to be monitored. The inverter calculates the maximum
motor speed on the basis of this parameter and the gear ratio.
③
–
Response when monitoring is activated. Further information on the stop responses
can be found in the section STOP reactions (Page 137).
– A functional description of monitoring can be found in the section Selecting SLS when
the motor is switched on (Page 24).
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA