Commissioning
4.4 Extended Safety
4.4.2.8

Parameterizing SLS

● Set the following in this screen:
● Close the screen.
4.4.2.9

Defining the F-DI status

If you do not want to transfer the status of the fail-safe inputs via PROFIsafe, go straight to
the section Activate settings (Page 101).
If you want to transfer the status of the fail-safe digital inputs via PROFIsafe, you first have to
configure the relevant PROFIsafe telegram; see the section Configuring communication in
STEP 7 (telegram 900) (Page 66). In STARTER, you then have to specify which F-DI-Status
you want to transfer via PROFIsafe.
100
Setpoint speed limit as a % of the monitoring threshold.
This parameter defines the upper speed limit when SLS is active.
Monitoring threshold
Enter the load-side speed to be monitored. The inverter calculates the maximum
motor speed on the basis of this parameter and the gear ratio.
Response when monitoring is activated. Further information on the stop responses
can be found in the section STOP reactions (Page 137).
– A functional description of monitoring can be found in the section Selecting SLS when
the motor is switched on (Page 24).
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA