XW Solar Charge Controller Installation

Removing the Wiring Compartment Cover

Removing Knockouts

4–4
6 inches (150 mm) on top and side(s)

Figure 4-1 Minimum Clearance Requirements

Before mounting, you must remove the wiring compartment cover to access the mounting
holes and the wiring terminals. The wiring compartment cover is secured with two
Phillips #8-32 × 2 ½-inch (63.5 mm) screws on the front cover of the unit. See Figure 4-2.
xantrex

Figure 4-2 Removing the Wiring Compartment Cover

Six dual and two single knockouts are provided for routing battery, PV array, BTS, and
network cables into the XW SCC. Bushings or conduits must be used to protect the wiring
from damage from rough edges around the knockout holes.
When removing knockouts, ensure that no metal shavings or fragments fall into the wiring
compartment.
Important:
Do not drill, cut, or punch holes in the XW SCC. Use only the knockouts provided
for conduit entry.
This manual for use by qualified personnel only
Remove screws to access
the field-wiring terminals.
975-0239-01-01