Making Ac Connections; Ac Connections And Communication Ports; Figure 2-14 Xw Inverter/Charger Ac Connections And Communications Ports - Xantrex XW4024-120/240-60 Installation Manual

Xw power system
Hide thumbs Also See for XW4024-120/240-60:
Table of Contents

Advertisement

Inverter/Charger Installation

Making AC Connections

AC Connections and Communication Ports

AC Connections
Communication
Ports
AC access
panel
AC OUT
AC IN
AC IN
L1
N
L2
L1
N
L2
L1
AC terminal
AC
GRID
GEN
(AC1)
(AC2)
LOAD
block

Figure 2-14 XW Inverter/Charger AC Connections and Communications Ports

2–16
This section describes how to make AC connections between the XW Inverter/Charger
and the XW Power Distribution Panel (using the pre-installed AC wiring in the XW
Power Distribution Panel) and between the XW Power Distribution Panel and the AC
distribution panel, or sub-panel (using wiring provided by the installer). See Appendix C,
"Alternate System Configurations" if the installation will not be including an XW Power
Distribution Panel.
CAUTION: Damage to the Inverter
The inverter's AC output must never be wired to the utility or generator output. This will cause
severe damage to the inverter which is not covered under warranty.
Do not use a GFCI equipped AC source to power either the grid or generator inputs. The
AC input filters on the XW may cause nuisance tripping of ground fault protected outputs.
The AC terminal block includes three terminals each (L1, L2 and Neutral) for AC Grid
input, AC Generator input, and AC Load connections. The neutrals are connected to each
other, requiring only one neutral connection when installed with an XW Power
Distribution Panel. Without the XW Power Distribution Panel, additional neutral
connections may be required at the input sources.
Four communications ports and one AUX Port are located on the bottom of the inverter
and support the following features.
The two AC sync ports are used for connecting multiple inverters in parallel.
The two Xanbus ports are used for network connections between inverters, charge
controllers, and accessories.
The AUX port provides 12 Vdc/250 mA output to control a relay, fan, indicator light
or other device. The auxiliary output can be configured (using a XW System Control
Panel) to trigger in response to low- or high-battery voltage or high- or low-battery
temperature. The auxiliary output can also be triggered manually using a XW System
Control Panel.
xantrex
Dual-knockouts
(¾"–1")
N
L2
Hybrid Inverter /Charger
This manual for use by qualified personnel only
Communications Ports
AC sync ports
Xanbus ports
(RJ45) (×2)
(RJ45) (×2)
AUX port
Bottom View
975-0239-01-01