Xw Power Distribution Panel Panel And Xw Conduit Box; Figure 1-4 Power Distribution Panel And Xw Conduit Box - Xantrex XW4024-120/240-60 Installation Manual

Xw power system
Hide thumbs Also See for XW4024-120/240-60:
Table of Contents

Advertisement

Introduction

XW Power Distribution Panel Panel and XW Conduit Box

XW Power Distribution Panel

Figure 1-4 Power Distribution Panel and XW Conduit Box

1–4
Internal wire barriers (or raceways) are included to keep communications wires separate
from AC and DC power wires. The XW Conduit Box also includes multiple cable strap
points.
The XW Power Distribution Panel (FGA: 865-1015) includes a mounting plate and XW
Conduit Box. It is factory wired and labelled with everything to support a code-compliant
single-inverter installation. It is designed to mount on the right side of the
inverter/charger, but it can also be configured to mount on the left side. Internal wiring
and breakers can be added to expand the XW Power System with up to three inverters,
four charge controllers, or other equipment to support 120/240-volt, 3-wire, single-phase
systems.
The XW Power Distribution Panel and XW Conduit Box interface with:
XW4024, XW4548, and XW6048 inverter/chargers
XW Solar Charge Controllers (requires customer supplied breakers and wiring)
C-Series Charge Controllers (requires customer supplied breakers and wiring).
Internal wire barriers (or raceways) are included to keep communications wires separate
from AC and DC power wires.
XW Power Distribution Panel includes:
Power Distribution Panel enclosure with a field-reversible panel door
Mounting Plate
XW Conduit Box
XW PDP Dimensions:
30" (761mm) H x 16" (406mm) W x 8 ¼" (210mm) D
Depth from the wall = 8 ¾" (223 mm)
The enclosure comes pre-wired with:
3x 60A, 120/240 Vac, 2-pole, Square-D, Type QOU, DIN-rail
mounted AC breakers (pre-wired to connect to one XW inverter)
1x GJ250A 160 Vdc, 3/8" stud DC breaker
2x Ground terminal bus bars
1x Neutral terminal bus bar
1x Negative bus bar
1 pair #4/0 AWG Battery Cables
The panel door can be mounted on the right or left side of the XW Power
Distribution Panel.
AC Knockout slots = 9 (for dual 60A Square D, type QOU breakers)*
DC Knockout slots = 8 small (for 60A DC breakers) and 3 large (for GJ breakers)
*AC Breakers cannot exceed 60A.
This manual for use by qualified personnel only
XW Conduit Box
Mounting Plate
975-0239-01-01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xw6048-120/240-6Xw4548-120/240-60

Table of Contents