Inverter/Charger Installation
Parts List for a Triple-Inverter Configuration
Converting a Single-Inverter Power Distribution Panel to a Triple-Inverter Power
Distribution Panel
2–36
❐ 1 x XW Power Distribution Panel (PDP) and Accessory kit (mounts to first unit).
❐ 1 x 865-1020 PDP Connection Kit for INV2.
The following items are required for the third inverter (furthest from PDP) and should be
sourced and prepared prior to the installation. (Note that all wiring will have to be custom
cut to fit the third unit. Wiring supplied with the extension kit is intended for a second
inverter in a two inverter system).
For a Single AC Source Installations:
❐ 1 x 865-1024 Conduit Box for inverter
❐ 1x 250 A DC breaker (Master packs available from Xantrex P/N: 865-1065)
❐ 1.0 m (39") x CAT5 network cable for inverter AC Sync
❐ 1.0 m (39") x CAT5 network cable for Xanbus communication
❐ 0.5m (20") x #4 AWG, 600 V, 105°C stranded green wire for ground connection
Or for a Dual AC Source Installations:
❐ 1 x 865-1020 Connectin Kit for INV2 (contains AC and DC breakers required for
third inverter).
❐ 2.3m (91") x #6 AWG, 600 V, 105°C Black stranded wire for L1 Gen (AC2).
❐ 2.3 m (91") x #6 AWG, 600 V, 105°C Red stranded wire for L2 Gen (AC2).
The following are required for both Single and Dual AC source Installations:
❐ 2.2 m (87") x #6 AWG, 600 V, 105°C stranded white wire for neutral
❐ 2.2 m (87") x #6 AWG, 600 V, 105°C Black stranded wire for L1 Grid (AC1).
❐ 2.2 m (87") x #6 AWG, 600 V, 105°C Red stranded wire for L2 Grid (AC1).
❐ 2.3m (91") x #6 AWG, 600 V, 105°C Black stranded wire for L1 (AC2 Load).
❐ 2.3 m (91") x #6 AWG, 600 V, 105°C Red stranded wire for L2 (AC2 Load).
❐ 2.4 m (95") x #6 AWG, 600 V, 105°C Red stranded wire for AC Load.
❐ 1.6m (62") #4/0 AGW, 105°C, Red stranded with #4/0 x 3/8 lugs crimped at each end
for the positive battery cable.
❐ 1.6m (62") #4/0 AGW, 105°C, Black stranded with #4/0 x 3/8 lugs crimped at each
end for the negative battery cable.
❐ External Bypass Switch - The XW Power Distribution Panel does not have enough
breaker locations to accommodate bypass breakers in a triple-inverter system.
Therefore, an external Bypass Switch may be needed. See Figure 2-34 on page 2–40
for an illustration of how to wire an External Bypass Switch.
◆ Remove upper wire cover and lower wire cover on the XW Power Distribution Panel.
This manual for use by qualified personnel only
975-0239-01-01