Inverter/Charger Installation

AC Wiring for a Triple-Inverter System

2–38
1. Prepare power distribution bars (supplied in 865-1020) by cutting away one of the
four tabs, only three tabs per power distribution bar are required in a three inverter
system. A total of 4 distribution bars should be prepared for a single AC source and 6
distribution bars for a dual AC source.
2. Mount the nine breakers on the din rail and install power distribution bars as follows
(refer to figures 2-28 & 2-29):
a) Two distribution bars, L1 and L2 at the input (top) terminals of the INV1, INV2
and INV3 Grid breakers.
b) If the installation includes a second AC source, install two distribution bars, L1
and L2 at the input (top) terminals of the INV1, INV2 and INV3 Gen breakers.
c) Two distribution bars, L1 and L2 at the output (bottom) terminals of the INV1,
INV2 and INV3 AC Load breakers.
3. Connect L1 and L2, AC wiring from each INV Grid breaker to the corresponding AC
Input (AC1) terminal on each of the three inverters.
4. If the installation includes a second AC source,, Connect L1 and L2, AC wiring from
each INV Gen breaker to the corresponding AC Input (AC2) terminal on each of the
three inverters.
5. Connect L1 and L2, AC wiring from each INV AC Load terminal from each of the
three inverters, to the corresponding AC INV Out breaker terminal in the PDP.
6. Connect L1 and L2, AC Load wiring to the INV Out (AC Load) power distribution
bar.
7. If the installation includes a second AC source, Connect L1 and L2, AC wiring from
the Generator (or other source) disconnect to the Gen breaker power distribution bars.
8. Connect L1 and L2, AC wiring from the Utility Grid distribution panel to the Grid
breaker power distribution bars.
9. Connect neutral wiring from INV1 (supplied with PDP), INV2 (supplied in 865-1050)
and INV3 (custom, see material list) to the neutral distribution bar in the PDP.
10. Connect ground wiring from INV1 (supplied with PDP), INV2 (supplied in 865-and
INV3 (user supplied for single AC source and included in 865-1050 for Dual AC
source) to the ground distribution bar in the PDP.
This manual for use by qualified personnel only