Inverter/Charger Installation
Wiring the Inverter to the XW Power Distribution Panel
Grounding the DC System
Actual grounding requirements may vary.
A
A
See Table 2-5 on page 2–10
for torque values for the AC
Chassis Ground.
Figure 2-9 DC Grounding Using a Power Distribution Panel
2–12
Important: If a XW Conduit Box is installed, communication and Battery Temperature Sensor
cables must run through the raceway at the rear of the XW Conduit Box. Before making AC and
DC connections, route all communication and Battery Temperature Sensor cables through the
raceways. The raceways becomes more difficult to access after all AC and DC wiring is completed.
The inverter's chassis ground bar (see Figure 2-9) is used to connect the chassis of the
inverter to the DC grounding system. The terminal accepts wires from #14 AWG to
#2 AWG.
This manual for use by qualified personnel only
B
B
B
See Table 2-6 on page 2–10
for torque values for the
Ground bars in the XW
Power Distribution Panel.