Importing An Scd File With Enervista Ur Setup - GE D60 Instruction Manual

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
The IED Section node describes the configuration of an IED.
IED Section (IED 1)
AccessPoint (name)
C
The following procedure describes how to update the D60 with the new configuration from an SCD file with the EnerVista
UR Setup software.
1.
Right-click anywhere in the files panel and select the Import Contents From SCD File item.
2.
Select the saved SCD file and click Open.
C-20
Server
Authentication (none)
LDevice (inst)
LN0 (InType, InClass, inst)
DataSet elements
ReportControl elements
Figure 0–9: SCD FILE STRUCTURE, IED NODE
D60 Line Distance Protection System
DOI elements
Inputs
ExtRef (iedName, ldInst, prefix, lnClass, lnInst, doName, daName, intAddr)
Other ExtRef elements
GSEControl elements
C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP
APPENDIX C
842794A1.CDR
GE Multilin