GE D60 Instruction Manual page 271

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
c) GROUND DISTANCE

PATH: SETTINGS
GROUPED ELEMENTS
 GROUND DISTANCE Z1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin

SETTING GROUP 1(6)
DISTANCE
GND DIST Z1
FUNCTION: Disabled
GND DIST Z1 DIR:
Forward
GND DIST Z1
SHAPE: Mho
GND DIST Z1
Z0/Z1 MAG: 2.70
GND DIST Z1
Z0/Z1 ANG: 0°
GND DIST Z1
ZOM/Z1 MAG: 0.00
GND DIST Z1
ZOM/Z1 ANG: 0°
GND DIST Z1
REACH: 2.00 Ω
GND DIST Z1
RCA: 85°
GND DIST Z1 REV
REACH: 2.00 Ω
GND DIST Z1 REV
REACH RCA: 85°
GND DIST Z1 POL
CURRENT: Zero-seq
GND DIST Z1 NON-
HOMOGEN ANG: 0.0°
GND DIST Z1
COMP LIMIT: 90°
GND DIST Z1
DIR RCA: 85°
GND DIST Z1
DIR COMP LIMIT: 90°
GND DIST Z1 QUAD
RGT BLD: 10.00 Ω
GND DIST Z1 QUAD
RGT BLD RCA: 85°
GND DIST Z1 QUAD
LFT BLD: 10.00 Ω
GND DIST Z1 QUAD
LFT BLD RCA: 85°
GND DIST Z1
SUPV: 0.200 pu
D60 Line Distance Protection System
5.6 GROUPED ELEMENTS

GROUND DISTANCE Z1(Z5)
Range: Disabled, Enabled
Range: Forward, Reverse, Non-directional
Range: Mho, Quad
Range: 0.00 to 10.00 in steps of 0.01
Range: –90 to 90° in steps of 1
Range: 0.00 to 7.00 in steps of 0.01
Range: –90 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: Zero-seq, Neg-seq
Range: –40.0 to 40.0° in steps of 0.1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.050 to 30.000 pu in steps of 0.001
5
5-137