GE D60 Instruction Manual page 592

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 32 of 60)
ADDR
REGISTER NAME
7B75
User Programmable Pushbutton 1 Off Text
7B7F
User Programmable Pushbutton 1 Drop-Out Time
7B80
User Programmable Pushbutton 1 Target
7B81
User Programmable Pushbutton 1 Events
7B82
User Programmable Pushbutton 1 LED Operand
B
7B83
User Programmable Pushbutton 1 Autoreset Delay
7B84
User Programmable Pushbutton 1 Autoreset Function
7B85
User Programmable Pushbutton 1 Local Lock
7B86
User Programmable Pushbutton 1 Message Priority
7B87
User Programmable Pushbutton 1 Remote Lock
7B88
User Programmable Pushbutton 1 Reset
7B89
User Programmable Pushbutton 1 Set
7B8A
User Programmable Pushbutton 1 Hold
7B8B
...Repeated for User Programmable Pushbutton 2
7BB6
...Repeated for User Programmable Pushbutton 3
7BE1
...Repeated for User Programmable Pushbutton 4
7C0C
...Repeated for User Programmable Pushbutton 5
7C37
...Repeated for User Programmable Pushbutton 6
7C62
...Repeated for User Programmable Pushbutton 7
7C8D
...Repeated for User Programmable Pushbutton 8
7CB8
...Repeated for User Programmable Pushbutton 9
7CE3
...Repeated for User Programmable Pushbutton 10
7D0E
...Repeated for User Programmable Pushbutton 11
7D39
...Repeated for User Programmable Pushbutton 12
7D64
...Repeated for User Programmable Pushbutton 13
7D8F
...Repeated for User Programmable Pushbutton 14
7DBA
...Repeated for User Programmable Pushbutton 15
7DE5
...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F06
Neutral Overvoltage 1 Target
7F07
Neutral Overvoltage 1 Events
7F08
Neutral Overvoltage 1 Curves
7F09
Reserved (8 items)
7F10
...Repeated for Neutral Overvoltage 2
7F20
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30
Auxiliary Overvoltage 1 Function
7F31
Auxiliary Overvoltage 1 Signal Source
7F32
Auxiliary Overvoltage 1 Pickup
7F33
Auxiliary Overvoltage 1 Pickup Delay
7F34
Auxiliary Overvoltage 1 Reset Delay
7F35
Auxiliary Overvoltage 1 Block
7F36
Auxiliary Overvoltage 1 Target
7F37
Auxiliary Overvoltage 1 Events
7F38
Reserved (8 items)
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
B-40
RANGE
---
0 to 60
0 to 2
0 to 1
0 to 65535
0 to 600
0 to 1
0 to 65535
0 to 2
0 to 65535
0 to 65535
0 to 65535
0 to 10
0 to 1
0 to 5
0 to 3.00
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 3
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 65535
D60 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
---
F202
s
0.05
F001
---
1
F109
---
1
F102
---
1
F300
s
0.05
F001
---
1
F102
---
1
F300
---
1
F220
---
1
F300
---
1
F300
---
1
F300
s
0.1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F116
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
(none)
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)
0
0 (Disabled)
0
0
0
1
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0 (Definite Time)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
GE Multilin