6 ACTUAL VALUES
PATH: ACTUAL VALUES
METERING
SYNCHROCHECK 1
MESSAGE
MESSAGE
The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-
abled", the corresponding actual values menu item will not be displayed.
PATH: ACTUAL VALUES
METERING
TRACKING FREQUENCY
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
Power System section of chapter 5 for additional details.
PATH: ACTUAL VALUES
METERING
FLEXELEMENT 1
The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT™ BASE UNITS
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
dcmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE ENERGY
(SRC X Positive and Negative
Watthours); (SRC X Positive and
Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
GE Multilin
SYNCHROCHECK
SYNCHROCHECK 1(2)
SYNCHROCHECK 1 DELTA
VOLT:
0.000 V
SYNCHROCHECK 1 DELTA
PHASE:
0.0°
SYNCHROCHECK 1 DELTA
FREQ:
0.00 Hz
TRACKING FREQUENCY
TRACKING FREQUENCY:
60.00 Hz
setting in the
SETTINGS
FLEXELEMENTS
FLEXELEMENT 1(8)
FLEXELEMENT 1
OpSig: 0.000 pu
2
× cycle
BASE = 2000 kA
BASE = maximum value of the
DCMA INPUT MAX
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
D60 Line Distance Protection System
6.3.4 TRACKING FREQUENCY
SYSTEM SETUP
POWER SYSTEM
setting for the two transducers configured
× I
for the +IN and –IN inputs
BASE
6.3 METERING
6.3.3 SYNCHROCHECK
menu. Refer to the
6.3.5 FLEXELEMENTS™
6-17
6