Synchrocheck; Tracking Frequency; Flexelements - GE D60 Instruction Manual

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

6 ACTUAL VALUES

PATH: ACTUAL VALUES
METERING
 SYNCHROCHECK 1
MESSAGE
MESSAGE
The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-
abled", the corresponding actual values menu item will not be displayed.

PATH: ACTUAL VALUES
METERING
 TRACKING FREQUENCY
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
Power System section of chapter 5 for additional details.

PATH: ACTUAL VALUES
METERING
 FLEXELEMENT 1
The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT™ BASE UNITS
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
dcmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE ENERGY
(SRC X Positive and Negative
Watthours); (SRC X Positive and
Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE

SYNCHROCHECK

(Max Delta Volts)
GE Multilin

SYNCHROCHECK
SYNCHROCHECK 1(2)
SYNCHROCHECK 1 DELTA
VOLT:
0.000 V
SYNCHROCHECK 1 DELTA
PHASE:
0.0°
SYNCHROCHECK 1 DELTA
FREQ:
0.00 Hz


TRACKING FREQUENCY

TRACKING FREQUENCY:
60.00 Hz
setting in the

SETTINGS


FLEXELEMENTS

FLEXELEMENT 1(8)
FLEXELEMENT 1
OpSig: 0.000 pu
2
× cycle
BASE = 2000 kA
BASE = maximum value of the
DCMA INPUT MAX
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
D60 Line Distance Protection System
6.3.4 TRACKING FREQUENCY

SYSTEM SETUP
POWER SYSTEM
setting for the two transducers configured
× I
for the +IN and –IN inputs
BASE
6.3 METERING
6.3.3 SYNCHROCHECK
menu. Refer to the
6.3.5 FLEXELEMENTS™
6-17