5 SETTINGS
Table 5–5: DIRECT INPUT AND OUTPUT DATA RATES
MODULE
CHANNEL
74
Channel 1
Channel 2
7L
Channel 1
Channel 2
7M
Channel 1
Channel 2
7P
Channel 1
Channel 2
7T
Channel 1
7W
Channel 1
Channel 2
7V
Channel 1
Channel 2
2A
Channel 1
2B
Channel 1
Channel 2
2G
Channel 1
2H
Channel 1
76
Channel 1
77
Channel 1
Channel 2
75
Channel 1
Channel 2
7E
Channel 1
Channel 2
7F
Channel 1
Channel 2
7G
Channel 1
Channel 2
7Q
Channel 1
Channel 2
7R
Channel 1
7S
Channel 1
Channel 2
The G.703 modules are fixed at 64 kbps. The
NOTE
The
DIRECT I/O CHANNEL CROSSOVER
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the
Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged.
GE Multilin
SUPPORTED DATA RATES
64 kbps
64 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps, 128 kbps
64 kbps
64 kbps
64 kbps
128 kbps
128 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
64 kbps
DIRECT I/O DATA RATE
setting applies to D60s with dual-channel communication cards and allows crossing
D60 Line Distance Protection System
5.2 PRODUCT SETUP
setting is not applicable to these modules.