Advertisement

5 SETTINGS
Table 5–9: D60 FLEXLOGIC™ OPERANDS (Sheet 7 of 10)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
SELECTOR 1 POS Y
Selector switch
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 2
ELEMENT:
SETTING GROUP ACT 1
Setting group
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
ELEMENT:
SRC1 50DD OP
Disturbance
SRC2 50DD OP
detector
SRC3 50DD OP
SRC4 50DD OP
ELEMENT:
SRC1 VT FUSE FAIL OP
VTFF (Voltage
SRC1 VT FUSE FAIL DPO
transformer fuse
SRC1 VT FUSE FAIL VOL LOSS
failure)
SRC2 VT FUSE FAIL to
SRC4 VT FUSE FAIL
ELEMENT:
SWITCH 1 OFF CMD
Disconnect switch
SWITCH 1 ON CMD
SWITCH 1 ΦA BAD ST
SWITCH 1 ΦA INTERM
SWITCH 1 ΦA CLSD
SWITCH 1 ΦA OPEN
SWITCH 1 ΦB BAD ST
SWITCH 1 ΦA INTERM
SWITCH 1 ΦB CLSD
SWITCH 1 ΦB OPEN
SWITCH 1 ΦC BAD ST
SWITCH 1 ΦA INTERM
SWITCH 1 ΦC CLSD
SWITCH 1 ΦC OPEN
SWITCH 1 BAD STATUS
SWITCH 1 CLOSED
SWITCH 1 OPEN
SWITCH 1 DISCREP
SWITCH 1 TROUBLE
SWITCH 2...
ELEMENT:
SYNC 1 DEAD S OP
Synchrocheck
SYNC 1 DEAD S DPO
SYNC 1 SYNC OP
SYNC 1 SYNC DPO
SYNC 1 CLS OP
SYNC 1 CLS DPO
SYNC 1 V1 ABOVE MIN
SYNC 1 V1 BELOW MAX
SYNC 1 V2 ABOVE MIN
SYNC 1 V2 BELOW MAX
SYNC 2
GE Multilin
OPERAND DESCRIPTION
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
Same set of operands as shown above for SELECTOR 1
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
Source 1 VT fuse failure detector has operated
Source 1 VT fuse failure detector has dropped out
Source 1 has lost voltage signals (V2 below 15% AND V1 below 5%
of nominal)
Same set of operands as shown for SRC1 VT FUSE FAIL
Disconnect switch 1 open command initiated
Disconnect switch 1 close command initiated
Disconnect switch 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase A is closed
Disconnect switch 1 phase A is open
Disconnect switch 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase B is closed
Disconnect switch 1 phase B is open
Disconnect switch 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase C is closed
Disconnect switch 1 phase C is open
Disconnect switch 1 bad status is detected on any pole
Disconnect switch 1 is closed
Disconnect switch 1 is open
Disconnect switch 1 has discrepancy
Disconnect switch 1 trouble alarm
Same set of operands as shown for SWITCH 1
Synchrocheck 1 dead source has operated
Synchrocheck 1 dead source has dropped out
Synchrocheck 1 in synchronization has operated
Synchrocheck 1 in synchronization has dropped out
Synchrocheck 1 close has operated
Synchrocheck 1 close has dropped out
Synchrocheck 1 V1 is above the minimum live voltage
Synchrocheck 1 V1 is below the maximum dead voltage
Synchrocheck 1 V2 is above the minimum live voltage
Synchrocheck 1 V2 is below the maximum dead voltage
Same set of operands as shown for SYNC 1
D60 Line Distance Protection System
5.5 FLEXLOGIC™