Data Logger - GE D60 Instruction Manual

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP

PATH: SETTINGS
PRODUCT SETUP
 DATA LOGGER
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
5
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Table 5–3: DATA LOGGER STORAGE CAPACITY EXAMPLE
SAMPLING RATE
15 ms
1000 ms
60000 ms
3600000 ms
Changing any setting affecting data logger operation will clear any data that is currently in the log.
NOTE
DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to "Continu-
ous", the data logger will actively record any configured channels at the rate as defined by the
5-40


DATA LOGGER

DATA LOGGER MODE:
Continuous
DATA LOGGER TRIGGER:
MESSAGE
Off
DATA LOGGER RATE:
MESSAGE
60000 ms
DATA LOGGER CHNL
MESSAGE
Off
DATA LOGGER CHNL
MESSAGE
Off
DATA LOGGER CHNL 16:
MESSAGE
Off
DATA LOGGER CONFIG:
MESSAGE
0 CHNL x
CHANNELS
DAYS
1
0.1
8
0.1
9
0.1
16
0.1
1
0.7
8
0.1
9
0.1
16
0.1
1
45.4
8
5.6
9
5
16
2.8
1
2727.5
8
340.9
9
303
D60 Line Distance Protection System
Range: Continuous, Trigger
Range: FlexLogic™ operand
Range: 15 to 3600000 ms in steps of 1
Range: Off, any FlexAnalog parameter. See Appendix A:
1:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
2:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Not applicable - shows computed data only
0.0 DAYS
STORAGE CAPACITY
954 s
120 s
107 s
60 s
65457 s
8182 s
7273 s
4091 s
3927420 s
490920 s
436380 s
254460 s
235645200 s
29455200 s
26182800 s
5 SETTINGS
5.2.9 DATA LOGGER
. The
DATA LOGGER RATE
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents