5 SETTINGS
f) DIRECTIONAL COMPARISON BLOCKING

PATH: SETTINGS
CONTROL ELEMENTS
 BLOCKING SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Generally, the scheme compares the direction to a fault at all terminals of the line. Unlike the permissive schemes, the
absence of a blocking signal permits operation of the scheme. Consequently, the scheme is biased toward dependability
and requires an "on/off" type of signaling.
By default this scheme uses only a forward-looking over-reaching zone 2 distance element to identify forward faults.
Ground directional overcurrent functions available in the relay can be used in conjunction with the zone 2 distance element
to increase the coverage for high-resistance faults. Also by default, only a reverse-looking zone 4 distance element to iden-
tify reverse faults. Ground directional overcurrent functions available in the relay can be used in conjunction with the zone 4
distance element for better time and sensitivity coordination.
For proper operation, the zone 2 and 4 phase and ground distance elements must be enabled, configured and set per rules
of distance relaying. If used by this scheme, the selected ground directional overcurrent functions must be enabled, config-
ured, and programmed accordingly.
In single-pole tripping applications, the scheme uses local fault type identification provided by the phase selector together
with information received from the remote terminal.
The scheme generates output operands (
control the transmission of signals to the remote end(s). When used with telecommunications facilities the output operands
should be assigned to operate output contacts connected to key the transmitter at the interface.
GE Multilin


PILOT SCHEMES
BLOCKING SCHEME
BLOCKING SCHEME
FUNCTION: Disabled
BLOCK SCHEME BLOCK:
Off
BLOCK RX CO-ORD PKP
DELAY: 0.010 s
TRANS BLOCK PICKUP
DELAY: 0.030 s
TRANS BLOCK RESET
DELAY: 0.090 s
BLOCK SCHEME SEAL-IN
DELAY: 0.010 s
GND DIR O/C FWD:
Off
GND DIR O/C REV:
Off
BLOCK SCHEME NO OF
COMM BITS: 1
BLOCK SCHEME RX1:
Off
BLOCK SCHEME RX2:
Off
BLOCK SCHEME RX3:
Off
BLOCK SCHEME RX4:
Off
BLOCK SCHEME EVENT:
Off
and
DIR BLOCK TX INIT
DIR BLOCK TX1 STOP
D60 Line Distance Protection System
5.7 CONTROL ELEMENTS
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 1, 2, or 4
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
through
DIR BLOCK TX4 STOP
5
) that
5-267