GE D60 Instruction Manual page 589

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 60)
ADDR
REGISTER NAME
713D
Ground Distance Zone 1 DIR RCA
713E
Ground Distance Zone 1 DIR Comp Limit
713F
Ground Distance Zone 1 Quad Right Blinder
7140
Ground Distance Zone 1 Quad Right Blinder RCA
7141
Ground Distance Zone 1 Quad Left Blinder
7142
Ground Distance Zone 1 Quad Left Blinder RCA
7143
Ground Distance Zone 1 Z0M Z1 Magnitude
7144
Ground Distance Zone 1 Z0M Z1 Angle
7145
Ground Distance Zone 1 Voltage Level
7146
Ground Distance Zone 1 Non-Homogeneous Angle
7147
Ground Distance Zone 1 POL Current
7148
Ground Distance Zone 1 Reverse Reach
7149
Ground Distance Zone 1 Reverse Reach RCA
714A
Reserved (7 items)
7151
...Repeated for Ground Distance Zone 2
7172
...Repeated for Ground Distance Zone 3
7193
...Repeated for Ground Distance Zone 4
71B4
...Repeated for Ground Distance Zone 5
Line Pickup (Read/Write Grouped Setting)
71F0
Line Pickup Function
71F1
Line Pickup Signal Source
71F2
Line Pickup Phase IOC Pickup
71F3
Line Pickup UV Pickup
71F4
Line End Open Pickup Delay
71F5
Line End Open Reset Delay
71F6
Line Pickup OV Pickup Delay
71F7
Autoreclose Coordination Pickup Delay
71F8
Autoreclose Coordination Reset Delay
71F9
Autoreclose Coordination Bypass
71FA
Line Pickup Block
71FB
Line Pickup Target
71FC
Line Pickup Events
71FD
Terminal Open
71FE
Autoreclose Accelerate
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260
Phase Directional Overcurrent 1 Function
7261
Phase Directional Overcurrent 1 Source
7262
Phase Directional Overcurrent 1 Block
7263
Phase Directional Overcurrent 1 ECA
7264
Phase Directional Overcurrent 1 Pol V Threshold
7265
Phase Directional Overcurrent 1 Block Overcurrent
7266
Phase Directional Overcurrent 1 Target
7267
Phase Directional Overcurrent 1 Events
7268
Reserved (8 items)
7270
...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7280
Neutral Directional Overcurrent 1 Function
7281
Neutral Directional Overcurrent 1 Source
7282
Neutral Directional Overcurrent 1 Polarizing
7283
Neutral Directional Overcurrent 1 Forward ECA
7284
Neutral Directional Overcurrent 1 Forward Limit Angle
7285
Neutral Directional Overcurrent 1 Forward Pickup
7286
Neutral Directional Overcurrent 1 Reverse Limit Angle
7287
Neutral Directional Overcurrent 1 Reverse Pickup
GE Multilin
RANGE
30 to 90
30 to 90
0.02 to 500
60 to 90
0.02 to 500
60 to 90
0 to 7
-90 to 90
0 to 5
-40 to 40
0 to 1
0.02 to 500
30 to 90
0 to 65535
0 to 1
0 to 5
0 to 30
0 to 3
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 65535
0 to 359
0 to 3
0 to 1
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 2
-90 to 90
40 to 90
0.002 to 30
40 to 90
0.002 to 30
D60 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
degrees
1
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
0.01
F001
degrees
1
F002
pu
0.001
F001
degrees
0.1
F002
---
1
F521
ohms
0.01
F001
degrees
1
F001
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F102
---
1
F167
---
1
F300
---
1
F001
pu
0.001
F001
---
1
F126
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F230
° Lag
1
F002
degrees
1
F001
pu
0.001
F001
degrees
1
F001
pu
0.001
F001
DEFAULT
85
90
1000
85
1000
B
85
0
0
0
0
0 (Zero-seq)
200
85
0
0 (Disabled)
0 (SRC 1)
1000
700
150
90
40
45
5
1 (Enabled)
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)
0 (SRC 1)
0
30
700
0 (No)
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Voltage)
75
90
50
90
50
B-37

Advertisement

Table of Contents
loading

Table of Contents