GE D60 Instruction Manual page 231

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
l) PMU RECORDING

PATH: SETTINGS
SYSTEM SETUP
 PMU 1
 RECORDING
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Each logical phasor measurement unit (PMU) is associated with a recorder. The triggering condition is programmed via the
menu. The recorder works with polar values using resolution as in the PMU actual values.
PMU 1 TRIGGERING
GE Multilin


PHASOR...
PHASOR MEASUREMENT UNIT 1
PMU 1 RECORDING
RATE: 10/sec
PMU 1 NO OF TIMED
RECORDS: 10
PMU 1 TRIGGER MODE:
Automatic Overwrite
PMU 1 TIMED TRIGGER
POSITION: 10%
PMU 1 REC PHS-1:
PMU 1 V1
PMU 1 REC PHS-1
NM: GE-UR-PMU-V1
PMU 1 REC PHS-14:
Off
PMU 1 REC PHS-14
NM: GE-UR-PMU-PHS-14
PMU 1 REC A-CH-1:
Off
PMU 1 REC A-CH-1
NM: AnalogChannel1
PMU 1 REC A-CH-8:
Off
PMU 1 REC A-CH-8
NM: AnalogChannel8
PMU 1 REC D-CH-1:
Off
PMU 1 REC D-CH-1
NM: DigitalChannel1
PMU 1 REC D-CH-16:
Off
PMU 1 REC D-CH-16
NM: DigitalChannel16
D60 Line Distance Protection System
5.4 SYSTEM SETUP

PMU 1 RECORDING
Range: 1, 2, 4, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times
per second
Range: 2 to 128 in steps of 1
Range: Automatic Overwrite, Protected
Range: 1 to 50% in steps of 1
Range: available synchrophasor values
Range: 16 character ASCII string
Range: available synchrophasor values
Range: 16 character ASCII string
Range: available FlexAnalog values
Range: 16 character ASCII string
Range: available FlexAnalog values
Range: 16 character ASCII string
Range: FlexLogic™ operand
Range: 16 character ASCII string
Range: FlexLogic™ operand
Range: 16 character ASCII string
5
5-97

Advertisement

Table of Contents
loading

Table of Contents