GE D60 Instruction Manual page 390

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS
In single-bit applications,
four-bit applications,
signals from two or more remote terminals should be connected through OR gates in the FlexLogic™ and the resulting
signals should be configured as the
SETTING
DUTT SCHEME
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
DUTT SCHEME BLOCK:
OFF = 0
FLEXLOGIC OPERANDS
PH DIST Z1 PKP
GND DIST Z1 PKP
SETTINGS
DUTT NO OF COMM
BITS:
DUTT RX1:
Off = 0
5
DUTT RX2:
Off = 0
DUTT RX3:
Off = 0
DUTT RX4:
Off = 0
5-256
must be used. In two-bit applications,
DUTT RX1
,
,
DUTT RX1
DUTT RX2
DUTT RX3
inputs.
DUTT RX
AND
AND
OR
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
OPEN POLE OP
SETTINGS
DUTT SEAL-IN
DELAY:
0
AND
OR
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
OPEN POLE OP
Figure 5–142: DUTT SCHEME LOGIC
D60 Line Distance Protection System
DUTT RX1
, and
must be used. In multi-terminal applications, the RX
DUTT RX4
DUTT NO OF COMM
BITS:
RUN
Phase
TRANSMIT TABLE
Selector
t
RST
DUTT NO OF COMM
BITS:
RUN
RX
Phase
TRIP TABLE
Selector
5 SETTINGS
and
must be used. In
DUTT RX2
FLEXLOGIC OPERANDS
DUTT TX1
DUTT TX2
DUTT TX3
DUTT TX4
FLEXLOGIC OPERAND
DUTT OP
FLEXLOGIC OPERANDS
DUTT TRIP A
DUTT TRIP B
DUTT TRIP C
DUTT TRIP 3P
837012AD.CDR