B.4 MEMORY MAPPING
bitmsk keypress
15
Message Up
16
Message Down
17
Message Left
18
Message Right
19
Menu
20
Help
B
21
Escape
22
---
F192
ENUMERATION: ETHERNET OPERATION MODE
0 = Half-Duplex, 1 = Full-Duplex
F194
ENUMERATION: DNP SCALE
0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000,
7 = 100000, 8 = 0.001
F195
ENUMERATION: SINGLE POLE TRIP MODE
0 = Disabled, 1 = 3 Pole Only, 2 = 3 Pole & 1 Pole
F196
ENUMERATION: NEUTRAL DIRECTIONAL OVERCURRENT
OPERATING CURRENT
0 = Calculated 3I0, 1 = Measured IG
F198
ENUMERATION: PILOT SCHEME COMMUNICATION BITS
0 = 1, 1 = 2, 2 = 4
F199
ENUMERATION: DISABLED/ENABLED/CUSTOM
0 = Disabled, 1 = Enabled, 2 = Custom
F200
TEXT40: 40-CHARACTER ASCII TEXT
20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F201
TEXT8: 8-CHARACTER ASCII PASSCODE
4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
F202
TEXT20: 20-CHARACTER ASCII TEXT
10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB
B-78
bitmsk keypress
43
User-programmable key 13
44
User-programmable key 14
45
User-programmable key 15
46
User-programmable key 16
47
User 4 (control pushbutton)
48
User 5 (control pushbutton)
49
User 6 (control pushbutton)
50
User 7 (control pushbutton)
D60 Line Distance Protection System
F203
TEXT16: 16-CHARACTER ASCII TEXT
F204
TEXT80: 80-CHARACTER ASCII TEXT
F205
TEXT12: 12-CHARACTER ASCII TEXT
F206
TEXT6: 6-CHARACTER ASCII TEXT
F207
TEXT4: 4-CHARACTER ASCII TEXT
F208
TEXT2: 2-CHARACTER ASCII TEXT
F211
ENUMERATION: SOURCE SELECTION
0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4,
5 = SRC 5, 6 = SRC 6
F213
TEXT32: 32-CHARACTER ASCII TEXT
F220
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY
value
priority
0
Disabled
1
Normal
2
High Priority
F222
ENUMERATION: TEST ENUMERATION
0 = Test Enumeration 0, 1 = Test Enumeration 1
F226
ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER
METHOD
0 = None, 1 = GSSE, 2 = GOOSE
F227
ENUMERATION: RELAY SERVICE STATUS
0 = Unknown, 1 = Relay In Service, 2 = Relay Out Of Service