9.1 DISTANCE ELEMENTS
× Z
+ I_0 × K0 × Z
I
A
L
L
× Z
+ I_0 × K0 × Z
I
A
L
L
Overcurrent supervision: | 3 × I_0 | = 4.09 A > 3 A
Reactance difference angle = | –3.9° – 24.8° | = 28.7° < 75°
Zero-sequence difference angle = | –19.8° – 0.0° | = 19.8° < 75°
Negative-sequence directional difference angle = | –19.8° – 0.0° | = 19.8° < 75°
Right blinder difference angle = | –93.0° – (–109.2°) | = 16.2° < 90°
Left blinder difference angle = | 82.9° – 108.7° | = 25.8° < 90°
Fault-type comparator difference angle = | 19.8° – 19.8° | = 0.0° < 50°
All six comparators and the overcurrent supervision are satisfied.
The Quad Phase A ground element will operate for this fault.
9
9-10
× K0M × Z
= 57.0 V ∠108.7°
+ I
– V
G
L
A
= 45.8 V ∠82.9°
D60 Line Distance Protection System
9 THEORY OF OPERATION