5 SETTINGS
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS
PRODUCT SETUP
 XCBR
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
setting represents the breaker operating counter. As breakers operate by opening and closing, the
CLEAR XCBR1 OpCnt
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XCBR1.
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
PRODUCT SETUP
 XSWI
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
setting represents the disconnect switch operating counter. As disconnect switches operate by
CLEAR XSWI1 OpCnt
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
NOTE
functionality.
GE Multilin


COMMUNICATIONS
IEC 61850 PROTOCOL
XCBR1 ST.LOC OPERAND
Off
XCBR2 ST.LOC OPERAND
Off
XCBR6 ST.LOC OPERAND
Off
CLEAR XCBR1 OpCnt:
No
CLEAR XCBR2 OpCnt:
No
CLEAR XCBR6 OpCnt:
No


COMMUNICATIONS
IEC 61850 PROTOCOL
XSWI1 ST.LOC OPERAND
Off
XSWI2 ST.LOC OPERAND
Off
XSWI24 ST.LOC OPERAND
Off
CLEAR XSWI1 OpCnt:
No
CLEAR XSWI2 OpCnt:
No
CLEAR XSWI24 OpCnt:
No
D60 Line Distance Protection System
5.2 PRODUCT SETUP

XCBR CONFIGURATION
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: No, Yes
Range: No, Yes
Range: No, Yes

XSWI CONFIGURATION
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: No, Yes
Range: No, Yes
Range: No, Yes