Advertisement

2.2 SPECIFICATIONS
BREAKER FLASHOVER
Operating quantity:
Pickup level voltage:
Dropout level voltage:
Pickup level current:
Dropout level current:
2
Level accuracy:
Pickup delay:
Time accuracy:
Operate time:
SYNCHROCHECK
Max voltage difference: 0 to 400000 V in steps of 1
Max angle difference:
Max freq. difference:
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
AUTORECLOSURE
Two breakers applications
Single- and three-pole tripping schemes
Up to 4 reclose attempts before lockout
Selectable reclosing mode and breaker sequence
PILOT-AIDED SCHEMES
Direct Underreaching Transfer Trip (DUTT)
Permissive Underreaching Transfer Trip (PUTT)
Permissive Overreaching Transfer Trip (POTT)
Hybrid POTT Scheme
Directional Comparison Blocking Scheme
Directional Comparison Unblocking Scheme (DCUB)
TRIP OUTPUT
Collects trip and reclose input requests and issues outputs to con-
Communications timer delay: 0 to 65535 s in steps of 0.001
Evolving fault timer:
Timing accuracy:
2-14
phase current, voltage and voltage differ-
ence
0 to 1.500 pu in steps of 0.001
97 to 98% of pickup
0 to 1.500 pu in steps of 0.001
97 to 98% of pickup
±0.5% or ±0.1% of rated, whichever is
greater
0 to 65.535 s in steps of 0.001
±3% or ±42 ms, whichever is greater
<42 ms at 1.10 × pickup at 60 Hz
°
0 to 100
in steps of 1
0.00 to 2.00 Hz in steps of 0.01
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
trol tripping and reclosing.
0.000 to 65.535 s in steps of 0.001
±3% or 4 ms, whichever is greater
D60 Line Distance Protection System
2 PRODUCT DESCRIPTION
POWER SWING DETECT
Functions:
Power swing block, Out-of-step trip
Characteristic:
Mho or Quad
Measured impedance:
Positive-sequence
Blocking / tripping modes: 2-step or 3-step
Tripping mode:
Early or Delayed
Current supervision:
Pickup level:
0.050 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Fwd / reverse reach (sec. Ω): 0.10 to 500.00 Ω in steps of 0.01
Left and right blinders (sec. Ω): 0.10 to 500.00 Ω in steps of 0.01
Impedance accuracy:
±5%
Fwd / reverse angle impedances: 40 to 90° in steps of 1
Angle accuracy:
±2°
Characteristic limit angles: 40 to 140° in steps of 1
Timers:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
LOAD ENCROACHMENT
Responds to:
Positive-sequence quantities
Minimum voltage:
0.000 to 3.000 pu in steps of 0.001
Reach (sec. Ω):
0.02 to 250.00 Ω in steps of 0.01
Impedance accuracy:
±5%
Angle:
5 to 50° in steps of 1
Angle accuracy:
±2°
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Time accuracy:
±3% or ±4 ms, whichever is greater
Operate time:
< 30 ms at 60 Hz
OPEN POLE DETECTOR
Functionality:
Detects an open pole condition, monitor-
ing breaker auxiliary contacts, the cur-
rent in each phase and optional voltages
on the line
Current pickup level:
0.000 to 30.000 pu in steps of 0.001
Line capacitive reactances (X
, X
C1
steps of 0.1
Remote current pickup level: 0.000 to 30.000 pu in steps of 0.001
Current dropout level:
pickup + 3%, not less than 0.05 pu
TRIP BUS (TRIP WITHOUT FLEXLOGIC™)
Number of elements:
6
Number of inputs:
16
Operate time:
<2 ms at 60 Hz
Time accuracy:
±3% or 10 ms, whichever is greater
): 300.0 to 9999.9 sec. Ω in
C0