GE D60 Instruction Manual page 164

Line distance protection system ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
The GGIO5 integer configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GGIO5 UINTEGER
 CONFIGURATION
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the D60. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger™ value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
5
 REPORT 1
 CONFIGURATION
Changes to the report configuration will not take effect until the D60 is restarted.
Disconnect any IEC 61850 client connection to the D60 prior to making setting changes to the report configuration.
Disconnecting the rear Ethernet connection from the D60 disconnects the IEC 61850 client connection.
NOTE
5-30

COMMUNICATIONS
GGIO5 UINT In
Off
GGIO5 UINT In
MESSAGE
Off
GGIO5 UINT 1n 16:
MESSAGE
Off

COMMUNICATIONS
REPORT 1
RptID:
REPORT 1
MESSAGE
OptFlds:
REPORT 1
MESSAGE
BufTm:
REPORT 1
MESSAGE
TrgOps:
REPORT 1
MESSAGE
IntgPd:
D60 Line Distance Protection System


IEC 61850...
GGIO5 ANALOG CONFIGURATION
Range: Off, any FlexInteger parameter
1:
Range: Off, any FlexInteger parameter
2:
Range: Off, any FlexInteger parameter


IEC 61850...
REPORT...
Range: up to 66 alphanumeric characters
Range: 0 to 65535 in steps of 1
0
Range: 0 to 4294967295 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 4294967295 in steps of 1
0
5 SETTINGS
REPORT 1(6) CONFIGURATION
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents