5 SETTINGS

PATH: SETTINGS
CONTROL ELEMENTS
 AUTORECLOSE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin

AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
AR MODE:
1 & 3 Pole
AR MAX NUMBER OF
SHOTS: 2
AR INITIATE MODE:
Protection AND CB
AR BLOCK BKR1:
Off
AR CLOSE TIME BKR 1:
0.10 s
AR BKR MAN CLOSE:
Off
AR BLK TIME UPON MAN
CLS:
10.00 s
AR 1P INIT:
Off
AR 3P INIT:
Off
AR 3P TD INIT:
Off
AR MULTI-P FAULT:
Off
BKR ONE POLE OPEN:
Off
BKR 3 POLE OPEN:
Off
AR 3-P DEAD TIME 1:
0.50 s
AR 3-P DEAD TIME 2:
1.20 s
AR 3-P DEAD TIME 3:
2.00 s
AR 3-P DEAD TIME 4:
4.00 s
AR EXTEND DEAD T 1:
Off
AR DEAD TIME 1
EXTENSION: 0.50 s
AR RESET:
Off
D60 Line Distance Protection System
5.7 CONTROL ELEMENTS
5.7.7 AUTORECLOSE
Range: Disabled, Enabled
Range: 1 & 3 Pole, 1 Pole, 3 Pole-A, 3 Pole-B
Range: 1, 2, 3, 4
Range: Protection AND CB, Protection Only
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand