APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 33 of 60)
ADDR
REGISTER NAME
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F67
Auxiliary Undervoltage 1 Target
7F68
Auxiliary Undervoltage 1 Events
7F69
Reserved (7 items)
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
Breaker Failure (Read/Write Grouped Setting) (2 modules)
8600
Breaker Failure 1 Function
8601
Breaker Failure 1 Mode
8602
Breaker Failure 1 Source
8603
Breaker Failure 1 Amp Supervision
8604
Breaker Failure 1 Use Seal-In
8605
Breaker Failure 1 Three Pole Initiate
8606
Breaker Failure 1 Block
8607
Breaker Failure 1 Phase Amp Supv Pickup
8608
Breaker Failure 1 Neutral Amp Supv Pickup
8609
Breaker Failure 1 Use Timer 1
860A
Breaker Failure 1 Timer 1 Pickup
860B
Breaker Failure 1 Use Timer 2
860C
Breaker Failure 1 Timer 2 Pickup
860D
Breaker Failure 1 Use Timer 3
860E
Breaker Failure 1 Timer 3 Pickup
860F
Breaker Failure 1 Breaker Status 1 Phase A/3P
8610
Breaker Failure 1 Breaker Status 2 Phase A/3P
8611
Breaker Failure 1 Breaker Test On
8612
Breaker Failure 1 Phase Amp Hiset Pickup
8613
Breaker Failure 1 Neutral Amp Hiset Pickup
8614
Breaker Failure 1 Phase Amp Loset Pickup
8615
Breaker Failure 1 Neutral Amp Loset Pickup
8616
Breaker Failure 1 Loset Time
8617
Breaker Failure 1 Trip Dropout Delay
8618
Breaker Failure 1 Target
8619
Breaker Failure 1 Events
861A
Breaker Failure 1 Phase A Initiate
861B
Breaker Failure 1 Phase B Initiate
861C
Breaker Failure 1 Phase C Initiate
861D
Breaker Failure 1 Breaker Status 1 Phase B
861E
Breaker Failure 1 Breaker Status 1 Phase C
861F
Breaker Failure 1 Breaker Status 2 Phase B
8620
Breaker Failure 1 Breaker Status 2 Phase C
8621
...Repeated for Breaker Failure 2
8642
...Repeated for Breaker Failure 3
8663
...Repeated for Breaker Failure 4
8684
...Repeated for Breaker Failure 5
86A5
...Repeated for Breaker Failure 6
GE Multilin
RANGE
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 65535
---
0 to 1
0 to 1
0 to 5
0 to 1
0 to 1
0 to 65535
0 to 65535
0.001 to 30
0.001 to 30
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 65535
0 to 65535
0 to 65535
0.001 to 30
0.001 to 30
0.001 to 30
0.001 to 30
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
D60 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
---
F001
---
1
F102
---
1
F157
---
1
F167
---
1
F126
---
1
F126
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
DEFAULT
0 (Disabled)
0 (SRC 1)
700
100
B
0 (Definite Time)
100
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)
0 (3-Pole)
0 (SRC 1)
1 (Yes)
1 (Yes)
0
0
1050
1050
1 (Yes)
0
1 (Yes)
0
1 (Yes)
0
0
0
0
1050
1050
1050
1050
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0
0
B-41