5 SETTINGS
Table 5–9: D60 FLEXLOGIC™ OPERANDS (Sheet 3 of 10)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
Dig Element 1 PKP
Digital elements
Dig Element 1 OP
Dig Element 1 DPO
Dig Element 2 to Dig Element 48
ELEMENT:
DIR BLOCK TX INIT
Blocking scheme
DIR BLOCK TX1 STOP
DIR BLOCK TX2 STOP
DIR BLOCK TX3 STOP
DIR BLOCK TX4 STOP
DIR BLOCK TRIP A
DIR BLOCK TRIP B
DIR BLOCK TRIP C
DIR BLOCK TRIP 3P
DIR BLOCK OP
ELEMENT:
DUTT TX1
DUTT
DUTT TX2
(Direct underreach
DUTT TX3
transfer trip)
DUTT TX4
DUTT TRIP A
DUTT TRIP B
DUTT TRIP C
DUTT TRIP 3P
DUTT OP
ELEMENT:
FxE 1 PKP
FlexElements™
FxE 1 OP
FxE 1 DPO
FxE 2 to FxE 8
ELEMENT:
GND DIST Z1 PKP
Ground distance
GND DIST Z1 OP
GND DIST Z1 OP A
GND DIST Z1 OP B
GND DIST Z1 OP C
GND DIST Z1 PKP A
GND DIST Z1 PKP B
GND DIST Z1 PKP C
GND DIST Z1 SUPN IN
GND DIST Z1 DPO A
GND DIST Z1 DPO B
GND DIST Z1 DPO C
GND DIST Z2 DIR SUPN
GND DIST Z2 to Z5
ELEMENT:
GROUND IOC1 PKP
Ground
GROUND IOC1 OP
instantaneous
GROUND IOC1 DPO
overcurrent
GROUND IOC2
ELEMENT:
GROUND TOC1 PKP
Ground time
GROUND TOC1 OP
overcurrent
GROUND TOC1 DPO
GROUND TOC2
ELEMENT:
HYBRID POTT TX1
Hybrid POTT
HYBRID POTT TX2
(Hybrid permissive
HYBRID POTT TX3
overreach transfer
HYBRID POTT TX4
trip)
HYBRID POTT TRIP A
HYBRID POTT TRIP B
HYBRID POTT TRIP C
HYBRID POTT TRIP 3P
HYBRID POTT OP
ELEMENT
LATCH 1 ON
Non-volatile latches
LATCH 1 OFF
LATCH 2 to LATCH 16
GE Multilin
OPERAND DESCRIPTION
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Same set of operands as shown for Dig Element 1
Directional blocking signal is initiated
Directional blocking scheme de-asserts transmit bit no. 1
Directional blocking scheme de-asserts transmit bit no. 2
Directional blocking scheme de-asserts transmit bit no. 3
Directional blocking scheme de-asserts transmit bit no. 4
Directional blocking scheme has operated to trip phase A
Directional blocking scheme has operated to trip phase B
Directional blocking scheme has operated to trip phase C
Directional blocking scheme has tripped all 3 phases
Directional blocking scheme has operated
Direct under-reaching transfer trip asserts transmit bit 1
Direct under-reaching transfer trip asserts transmit bit 2
Direct under-reaching transfer trip asserts transmit bit 3
Direct under-reaching transfer trip asserts transmit bit 4
Direct under-reaching transfer trip has operated to trip phase A
Direct under-reaching transfer trip has operated to trip phase B
Direct under-reaching transfer trip has operated to trip phase C
Direct under-reaching transfer trip has operated to trip all three phases
Direct under-reaching transfer trip has operated
FlexElement™ 1 has picked up
FlexElement™ 1 has operated
FlexElement™ 1 has dropped out
Same set of operands as shown for FxE 1
Ground distance zone 1 has picked up
Ground distance zone 1 has operated
Ground distance zone 1 phase A has operated
Ground distance zone 1 phase B has operated
Ground distance zone 1 phase C has operated
Ground distance zone 1 phase A has picked up
Ground distance zone 1 phase B has picked up
Ground distance zone 1 phase C has picked up
Ground distance zone 1 neutral is supervising
Ground distance zone 1 phase A has dropped out
Ground distance zone 1 phase B has dropped out
Ground distance zone 1 phase C has dropped out
Ground distance zone 2 directional is supervising
Same set of operands as shown for GND DIST Z1
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
Same set of operands as shown for GROUND IOC 1
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
Same set of operands as shown for GROUND TOC1
Hybrid permissive over-reaching transfer trip asserts transmit bit 1
Hybrid permissive over-reaching transfer trip asserts transmit bit 2
Hybrid permissive over-reaching transfer trip asserts transmit bit 3
Hybrid permissive over-reaching transfer trip asserts transmit bit 4
Hybrid permissive over-reaching transfer trip has operated to trip phase A
Hybrid permissive over-reaching transfer trip has operated to trip phase B
Hybrid permissive over-reaching transfer trip has operated to trip phase C
Hybrid permissive over-reaching transfer trip has tripped all three phases
Hybrid permissive over-reaching transfer trip has operated
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
Same set of operands as shown for LATCH 1
D60 Line Distance Protection System
5.5 FLEXLOGIC™
5
5-105