Importing An Scd File With Enervista Ur Setup - GE UR Series C70 Instruction Manual

Capacitor bank protection and control system
Table of Contents

Advertisement

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
The IED Section node describes the configuration of an IED.
IED Section (IED 1)
AccessPoint (name)
C
The following procedure describes how to update the C70 with the new configuration from an SCD file with the EnerVista
UR Setup software.
1.
Right-click anywhere in the files panel and select the Import Contents From SCD File item.
2.
Select the saved SCD file and click Open.
C-20
Server
Authentication (none)
LDevice (inst)
LN0 (InType, InClass, inst)
DataSet elements
ReportControl elements
Figure 0–9: SCD FILE STRUCTURE, IED NODE
C70 Capacitor Bank Protection and Control System
DOI elements
Inputs
ExtRef (iedName, ldInst, prefix, lnClass, lnInst, doName, daName, intAddr)
Other ExtRef elements
GSEControl elements
C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP
APPENDIX C
842794A1.CDR
GE Multilin

Advertisement