64-Point Type Dc Input Unit - Panasonic fp2/fp2sh User Manual

Programmable controller
Table of Contents

Advertisement

FP2/FP2SH
2.9.3

64-point Type DC Input Unit

Specifications
Item
Part number
Insulation method
Rated input voltage
Rated input current
Input impedance
Input voltage range
Min. on voltage/Min. on current
Max. off voltage/Max. off current
Response time
p
Internal current consumption (at 5V DC)
Common method (Input points per common) 32 points/common
Operating indicator
External connection method
Weight
Note
Keep the number of input points per common which are simulta-
neously on within the following range as determined by the input
voltage and ambient temperature.
Number of
points per
common which
are simulta-
neous on
Description
FP2−X64D2
Optical coupler
24V DC
Approx. 4.3mA (at 24V DC)
Approx. 5.6kΩ
20.4 to 26.4V DC
19.2V/4mA
5.0V/1.5mA
off → on
0.2ms or less
on → off
0.3ms or less
100mA or less
Either the positive or negative of the input power supply can be
connected to common terminal.
32-dot LED display (lit when on, switching)
Connectors (MIL type two 40-pin)
Approx. 120g
50/
127.4
Ambient temperature (°C/°F)
2.9
Input Units Specifications
26.4V DC
24V DC
55/
131
Parts and Functions
2 − 37

Advertisement

Table of Contents
loading

Table of Contents