Panasonic fp2/fp2sh User Manual page 274

Programmable controller
Table of Contents

Advertisement

Setting the number of timers and counter (system register 5)
Timers and counters share the same area. If the method of dividing the area is changed, the number of
timers and counters will also change.
Type
FP2
1,024 points
FP2SH/FP10SH
3,072 points
For FP2/FP2SH, set the system registers 5 and 6 to the same value. This sets the timer to a non-hold
-
type and counter to a hold type.
By setting system register 5 to "0", the whole area becomes the counter. Also, by setting it to the value
-
1 higher than the last number, the whole area becomes the timer.
Hold type area starting address (system registers 6 to 13)
Set each relay and register to a hold type or non-hold type.
For normal situations, set the system registers 5 and 6 to the same value. This sets the timer to a non-
-
hold type and counter to a hold type.
By setting this value to the first number, the whole area becomes hold type. Also, by setting it to the
-
value 1 higher than the last number, the whole area becomes non-hold type.
The relays and registers for links not specified in the send area of system registers 40 to 55 are non-
-
hold type regardless of what is set here.
11-6
Total point
Default value of
numbers
system register 5
1000
3000
Timer
1000 points
24 points
(No. 0 to 999)
(No. 1000 to 1023)
3000 points
72 points
(No. 0 to 2999)
(No. 3000 to 3071)
Counter