10.2 Performance Specifications
10.2.1 Input Specifications of the Analog Input Unit
■
Input specifications
Item
No. of input points
Input range
(resolution)
Conversion speed
Exceeding the rated range
Total accuracy
Input impedance
Absolute max. input
Insulation method
Execution / Non-execution
channel settings
Input range selection
Average
processing
Offset / Gain settings
Scale conversion settings
WUME-GM1AIO-01
Specifications
8 ch
Voltage
-10 to +10 V DC (Resolution: 1/64,000)
0 to +10 V DC (Resolution: 1/32,000)
-5 to +5 V DC (Resolution: 1/64,000)
0 to +5 V DC (Resolution: 1/32,000)
+1 to +5 V DC (Resolution: 1/25,600)
Current
0 to +20 mA (Resolution: 1/32,000)
+4 to +20 mA (Resolution: 1/25,600)
50 μs/ch
Possible to output up to the rated value ± 2%
With the 0 to 20 mA range, the lower limit is not supported for exceeding the
rated range.
±0.2%F.S. or less (at +25℃)
±0.4%F.S. or less (at 0 to +55℃)
Voltage input: Approximately 1 MΩ; current input: Approximately 250 Ω
Voltage input: -15 V to +15 V; current input: -30 mA to +30 mA
Between input terminals and internal circuit: Photocoupler and isolated
DC/DC converter
Between channels: Non-insulated
Possible to make non-converted channel settings.
Possible to make settings on a channel-by-channel basis
Number of
Setting range of 2 to 60,000 times
averaging
times
Time
Time setting range of 1 to 1,500 ms
average
Moving
Setting range of 2 to 2,000 times
average
A desired value within the digital output range can be set for the offset
value.
Setting range: -3000 to +3000
A desired value within the digital output range can be set for the gain value.
Setting range: +9,000 to +11,000 (90% to 110%)
A desired value within the digital output range can be set for the scale
conversion setting value.
Setting range: -32768 to +32767
10.2 Performance Specifications
(Note 1)
(Note 2)
(Note 1)
10-3