4.2

Power Supply Wiring

4.2.1

Wiring of Power Supply

Pin layout of power supply unit (FP2−PSA1 is used for the example below.)
Use separate systems for the power
devices and the input devices.
Breaker
Use an insulated transformer
when effects from noise are
great.
Power supply voltage
Verify that the power supply voltage connected to the power supply unit is within allow-
able limits.
Type
Part number
AC type
yp
FP2−PSA1
FP2−PSA2
FP2−PSA3
DC type
FP2−PSD2
Power supply wire
Use power supply wire that is thicker than 2mm
Pressure connection terminal
The following M3 pressure connection terminals are recommended for the wiring.
Fork type terminal
6mm/0.236in.
or less
3.2mm/0.126in. or more
Power supply terminals
Supplies 100 to 120V AC.
2
Use 2mm
(AWG14) twisted pair
cable or larger.
Ground terminal
ALARM output terminals
An alarm output can be
output when the ALARM
condition occurs
(
section 4.6.3).
Grounding
Rated input
Operating voltage rage
voltage
100 to 120V AC
85 to 132V AC
200 to 240V AC
170 to 264V AC
100 to 240V AC
85 to 264V AC
24V DC
20.4 to 31.2V DC
6mm/0.236in.
or less
4.2
2
(AWG14) to minimize the voltage drop.
Round type terminal
3.2mm/0.126in. or more
Installation and Wiring
Power Supply Wiring
Rated output current
2.5A
2.5A
5A
5A
next page
4 − 15