Panasonic fp2/fp2sh User Manual page 358

Programmable controller
Table of Contents

Advertisement

Error
Name
code
System
watching
E43
dog timer
error
Slave
station
connecting
E44
time error
for
MEWNET-F
system
Operation
E45
error
11-90
Opera-
tion
Description and steps to take
status
Scan time required for program execution
exceeds the setting of the system watching
dog timer.
⇒ Check the program and modify it so that
Selec-
the program can execute a scan within the
specified time.
table
Selection of operation status using system
register24:
-to continue operation, set 1
-to stop operation, set 0
The time required for slave station
connection exceeds the setting of the system
register 35.
Selec-
Selection of operation status using system
table
register25:
-to continue operation, set 1
-to stop operation, set 0
Operation became impossible when a high-
level instruction was executed.
Selection of operation status using system
register26:
-to continue operation, set K1
-to stop operation, set K0
The address of operation error can be
confirmed in either special data registers
Selec-
DT9017 and DT9018, or DT90017 and
DT90018. (It varies according to the model to
table
be used.)
DT9017, DT9018: FP-e, FP0,
DT90017, DT90018: FP∑, FP-X,
Verification is possible in FPWIN GR/Pro at
"I/O error" in the status display function.
FP0R(FP0 mode)
FP0R(FP0R mode),
FP2, FP2SH, FP10SH
A
A
A
A
A
A
A
A: Available
A
A
A
A
A
A

Advertisement

Table of Contents
loading

Table of Contents