This group of addresses is used to map the eight possible low zone tampers to one of the four possible reporting
scenarios. If a value of zero (0) is assigned at an address in this block, low tampers from that zone input will not be
reported by the communicator. Low Zone Tamper is a short circuit input.
P481E
1-4E
Low Zone 1 Tamper Alarms mapped to Scenario 1-4 - Default 1
P482E
1-4E
Low Zone 2 Tamper Alarms mapped to Scenario 1-4 - Default 1
P483E
1-4E
Low Zone 3 Tamper Alarms mapped to Scenario 1-4 - Default 1
P484E
1-4E
Low Zone 4 Tamper Alarms mapped to Scenario 1-4 - Default 1
P485E
1-4E
Low Zone 5 Tamper Alarms mapped to Scenario 1-4 - Default 1
P486E
1-4E
Low Zone 6 Tamper Alarms mapped to Scenario 1-4 - Default 1
P487E
1-4E
Low Zone 7 Tamper Alarms mapped to Scenario 1-4 - Default 1
P488E
1-4E
Low Zone 8 Tamper Alarms mapped to Scenario 1-4 - Default 1
HIGH ZONE TAMPERS SCENARIO MAPPING - P491E - P498E
This group of addresses is used to map the eight possible High zone tampers to one of the four possible reporting
scenarios. If a value of zero (0) is assigned at an address in this block, high tampers from that zone input will not
be reported by the communicator. High Zone Tamper is an open circuit input.
P491E
1-4E
High Zone 1 Tamper Alarms mapped to Scenario 1-4 - Default 1
P492E
1-4E
High Zone 2 Tamper Alarms mapped to Scenario 1-4 - Default 1
P493E
1-4E
High Zone 3 Tamper Alarms mapped to Scenario 1-4 - Default 1
P494E
1-4E
High Zone 4 Tamper Alarms mapped to Scenario 1-4 - Default 1
P495E
1-4E
High Zone 5 Tamper Alarms mapped to Scenario 1-4 - Default 1
P496E
1-4E
High Zone 6 Tamper Alarms mapped to Scenario 1-4 - Default 1
P497E
1-4E
High Zone 7 Tamper Alarms mapped to Scenario 1-4 - Default 1
P498E
1-4E
High Zone 8 Tamper Alarms mapped to Scenario 1-4 - Default 1
SYSTEM EVENTS SCENARIO MAPPING - P311E - P320E
This group of addresses is used is used to map the ten possible System Events as listed below to one of the four
possible reporting scenarios. If a value of zero (0) is assigned at an address in this block, that event will not be
reported by the communicator.
P311E
1-4E
Keypad Panic mapped to Scenario 1-4 - Default 1
P312E
1-4E
Battery low mapped to Scenario 1-4 - Default 1
P313E
1-4E
230v Mains failure mapped to Scenario 1-4 - Default 1
P314E
1-4E
Phone line restore mapped to Scenario 1-4 - Default 1
P315E
1-4E
Radio PIR Battery Low mapped to Scenario 1-4 - Default 1
P316E
1-4E
Radio Key Battery Low mapped to Scenario 1-4 - Default 1
P317E
1-4E
Keypad Tamper mapped to Scenario 1-4 - Default 1
P318E
1-4E
Cabinet Tamper mapped to Scenario 1-4 - Default 1
P319E
1-4E
Radio Panic mapped to Scenario 1-4 - Default 1
P320E
1-4E
Communicator Test Calls mapped to Scenario 1-4 - Default 1
REPORT DELAY ON MAINS FAIL
P460E
1-99E
Mains failure report delay 0-99 minutes - Default = 60