1-8E
Zone is a handover - Where options 1-8 represent zones 1-8. Zones defined at this address as
handover are given the unique ability to behave as both delay and instant zones. If a zone
defined as an entry delay zone has been activated and the entry delay is running, a handover
zone will behave as another entry delay zone with a delay time as defined at P401E to P416E.
If an entry delay zone has not been activated and there is no entry delay running, a handover
zone becomes an instant zone with no entry delay. (Default 2) The Handover zone MUST
have an entry delay programmed.
P337E
1-8E
Two Trigger Zones - Where options 1-8 represent zones 1-8. A zone defined as two trigger at
this address will only cause an activation if one of the following conditions are met;
a
P452E or P453E
b
as defined by Address P451E, P452E or P453E
c
defined by Address P451E, P452E or P453E
P338E
1-8E
Zone is 24 Hour - Where options 1-8 represent zones 1-8. 24 hour zones will activate whether
the panel or partition is set or unset. The entry delay can also be assigned. (Default none)
P339E
1-8E
Monitor Mode Zones - Where options 1-8 represent zones 1-8. Zones included at this address
will become active when the panel is in Monitor Mode. Zones not assigned at this address will
be excluded. (Default 1-4) Note: Monitor Mode Zones are linked to Area assignments
P340E
1-8E
Day Zones - Where options 1-8 represent zones 1-8. Day zones are active during periods
where the panel or partitions are unset and revert to normal zones during set periods (Default
none)
P341E
1-8E
Siren Lockout Zones - Where options 1-8 represent zones 1-8. Zones with siren lockout
designation will only cause their assigned outputs to operate once per armed period. Led on =
zone locked out. (Default none)
P342E
1-8E
Auto Exclude Zones - Where options 1-8 represent zones 1-8. Zones assigned Auto Exclude
function at this address will be automatically excluded by the system if they are unsealed when
the exit timers expire. Zones not given Auto Exclude status will cause an activation if they are
unsealed at the end of the exit delay period. (Default all on)
P343E
1-8E
Access Control door position input - Where options 1-8 represent zones 1-8. (Default none)
P344E
1-8E
Access Control Request to exit input - Where options 1-8 represent zones 1-8. (Default
none)
P345E
1-8E
Continuous Day Zone - Where options 1-8 represent zones 1-8. The zone acts as a dayzone at
all times (Armed and Disarmed) and will operate day alarms but not normal zone alarms (Default
none)
P346E
1-8E
Zone will report multiple activations to communicator - Default 1-8
Where addresses P331E through P346E relate to
the 8 low zones, addresses P351E through P366E define the
same options but relate to the 8 high zones
The zone is triggered twice within the two trigger time period as defined by Address P451E,
Any two zones defined as two trigger activate once each within the two trigger time period
A zone defined as two trigger is left violated for longer than the two trigger time period as
Page 31