P170E
1-8
Time Zone to use for Auto Arm or Disarm (Default 0) - This option will determine which Time
Zone will cause Area "A" to arm, disarm or both, based on the programmed options set at
P180E.
PARTITION "A" PRIMARY OUTPUT OPTIONS first set - P171E - P178E
This block of addresses sets a number of output options which are specific and unique to the operation of partition
or Area "A". Activity in Areas "B" or "C" will have NO direct effect on the options set at these addresses.
P171E
1E
Normal zone alarms to output #1
2E
24 hour alarms to output #1
3E
Monitor Mode alarms to output #1
4E
Pendant chirps to output #1
5E
All zones sealed indication to output #1
6E
2 second pulse on arming or disarming to output #1
7E
Intelligent smoke reset pulse to output #1
8E
Day zone alarms to output #1
Option 1
Normal zone alarms to output #1 - This option will map activation from normal zone alarms from
Area "A" to output #1. Normal zones are those which will only activate when the partition is armed
(Set)
Option 2
24 Hour alarms to output #1 - This option will map activations from zones defined as Area "A" 24
Hour to output #1. Zones are defined as 24 Hour at P338E and P358E
Option 3
Monitor Mode alarms to output #1 - This option will map activations from zones defined as Area "A"
Monitor Mode to output #1. Zones are defined as Monitor Mode at P339E and P359E
Option 4
Pendant Chirps to output #1 - This option will map two short pulses (Chirps) to output #1 when Area
"A" is set via a radio key (Pendant) and four short pulses to output #1 when Area "A" is unset again.
Option 5
All zones sealed indication to output #1 - This option will map a Area "A" safe indication to output
#1. A safe indication is produced when all zones in an area are sealed, i.e. zone lights off.
Option 6
2 second pulse to output #1 on arming or disarming - This option will map a 2 second pulsed
output at Output #1 each time Area"A" is armed or disarmed as defined at P199E options 6&7.
Option 7
Intelligent Smoke Reset pulse to output #1 - This option is similar to option 6 in that it produces a
momentary pulse at the output when Area "A" is armed and is used to reset latching smoke detectors.
The difference is that this option will only produce a pulsed output if a 24 Hour zone in Area "A" has
been activated during the previous armed period.
Option 8
Day zone alarms to output #1 - The option will map activations from Area "A" zones defined as Day
Zones to output #1. Zones are defined as Day Zones at P340E and P360E. Day zones are those
which operate only during periods when the Area is disarmed and are normally used as door bells and
shop minders etc.
Note: P172E through P178E are as above but applied to outputs 2-8
Option 7 MUST be used on systems where ESL brand 449 series smoke detectors are installed rather than
option 6. This is due to the way in which the 449 series detectors perform a "self check" function every 24
hours. Interrupting the power supply to these detectors restarts their internal timer and in normal system
Page 24