P343E is used to assign a zone to be the door position monitor input and address P344E is used to assign a zone
as the request to exit input. Once options have been programmed, a door which is fitted with a reed switch,
monitored by the zone as defined at P343E will cause a 24 hour alarm if it is opened without the Control Function
being operated. Once the control function has been operated with a valid code, a door open too long (DOTL) timer
is started and if the door is not closed again within the time determined by P454E (Area "A"), P455E (Area "B:) or
P456E (Area "C") a 24Hr alarm will be created. The control function to output mapping is defined at addresses
P181E through P188E for Area "A".
P454E
1-999E
Area "A" door open too long time period - default 10 sec
P455E
1-999E
Area "B" door open too long time period - default 10 sec
P456E
1-999E
Area "C" door open too long time period - default 10 sec
P460E
1
-
9
9
Delay
Mains
Fail Report - where the option value between 0 and 99 represent time delays
value of 0 will result in an instant report of mains failure
(Default = 60)
P450E
1-99E
Report Delay on Zones - this delay pauses the zone reporting of alarms via the
communicator for the programmed period (0 = No delay, 1-99 seconds). If the alarm is reset
before this delay expires no alarms will be reported.