3-Phase 3-Wire Power Networks; 3-Phase 3-Wire ∆ (With 2 Current Sensors); 3-Phase 3-Wire ∆ (With 3 Current Sensors) - AEMC PEL102 User Manual

Power energy logger
Hide thumbs Also See for PEL102:
Table of Contents

Advertisement

3.6.3 3-Phase 3-Wire Power networks

3.6.3.1 3-Phase 3-Wire ∆ (with 2 current sensors)
For 3-Phase 3-Wire
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal V2 test lead to the L2 phase
conductor
Connect the terminal V3 test lead to the L3 phase
conductor
Connect the terminal I1 current probe to the LI phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed towards
the load. This ensures proper phase angle for power measure-
ments and other phase sensitive measurements.
3.6.3.2 3-Phase 3-Wire ∆ (with 3 current sensors)
For 3-Phase 3-Wire
Connect the terminal V1 test lead to the L1 phase conductor
Connect the terminal V2 test lead to the L2 phase conductor
Connect the terminal V3 test lead to the L3 phase conductor
Connect the terminal I1 current probe to the LI phase
conductor.
Connect the terminal I2 current probe to the L2 phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed towards the
load. This ensures proper phase angle for power measurements
and other phase sensitive measurements.
22
Find Quality Products Online at:
measurements using two current sensors:
measurements using three current sensors:
GlobalTestSupply
www.
L3
L2
L 1
V1
V2
V3
N
I1
Figure 14
L3
L2
L 1
V1
V2
V3
N
I1
Figure 15
Power & Energy Logger Model PEL 102 and PEL 103
.com
sales@GlobalTestSupply.com
L1
L2
L3
I2
I3
L1
L2
L3
I2
I3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pel103Pel 102

Table of Contents