Servicing the Front LED Indicator Module (FRU)

The following section describes how to service the front LED indicator module. The front LED
indicator module is a field-replaceable unit (FRU). For more information about FRUs, see
"Illustrated Parts Breakdown" on page 20
Ensure that all power is removed from the server before removing or installing a
Caution -
front LED indicator module. You must disconnect the power cables before performing this
procedure.
The front LED indicator modules should be removed and replaced only by authorized
Caution -
Oracle Service personnel.
This section covers the following procedures:
"Remove the Front LED Indicator Module" on page 165
"Install the Front LED Indicator Module" on page 168
Related Information
"Troubleshooting Using the Server Front and Back Panel Status Indicators" on page 28

Remove the Front LED Indicator Module

Prepare the server for service.
1.
a.
Power off the server and disconnect the power cords from the power
supplies.
See
"Powering Down the Server" on page
b.
Extend the server into the maintenance position.
and
"Field-Replaceable Units" on page
53.
Servicing the Front LED Indicator Module (FRU)
22.
165