2.10.15 Modbus Communication Log (FLog)

IM 04L51B01-17EN
The output in response to the command "FLog,Modbus" is shown below.
Syntax
EA<crlf>
yyyy/mo/dd_hh:mm:ss_c_xxxxxx_kkk...k_nnn_d<crlf>
...
EN<crlf>
yyyy/mo/dd_hh:mm:ss Time of error occurrence
c
Communication type
xxxxxx
Event that occurred (fixed to 6 characters)
kkk...k
Details (fixed to 15 characters. Unused character positions are
filled with spaces. See table below.)
nnn
Command number (0 to 999)
d
Command type
*
Detail
Meaning
SKIP
Command not set.
INVALID
Command cannot be executed.
WAITING
Server/slave communication recovery wait.
CLOSED
Server/slave connection closed.
RESOLVING
Server/slave connection being established (resolving address).
Server/slave connection being established (requesting connection).
CONNECTING
Server/slave connection failed (peer not found).
UNREACH
TIMEDOUT
Server/slave connection failed (timeout occurred).
BROKEN
Response message corrupt (CRC error).
ERR_FC
Response message was an illegal function message.
ERR_ADDR
Response message was an illegal data address message.
ERR_VALUE
Response message was an illegal data value message.
Response message was a slave device failure message
ERR_DEVICE
ERR_ACK
Response message was an acknowledge message.
ERR_BUSY
Response message was a slave device busy message.
ERR_NEGATIVE
Response message was a negative acknowledge message.
ERR_GATE_PATH
Response message was a gateway path unavailable message.
Response message was a gateway target device failed to respond
ERR_GATE_TARGET
message.
BAD_SLAVE
The slave address of the response message is invalid (does not
match the command).
BAD_FC
The function code of the response message is invalid (does not
match the command).
yyyy
Year (1900 to 2099)
mo
Month (01 to 12)
Day (01 to 31)
dd
Hour (00 to 23)
hh
mm
Minute (00 to 59)
ss
Second (00 to 59)
M
Modbus master
C
Modbus client
Activated
ACTIVE
READY_
Command ready state
CLOSE_
Disconnected
HALT_¯
Command halted
_¯_¯_¯
Other than those above
R
Read
Write
W
O
Write immediately (write from the custom display)
N
Miscellaneous
2.10 ASCII Output Format
2-139
1
2
App