Smart Dc: Photo Eye / Reflecti-Guard (Rg-R) - HySecurity UL 325 Quick Start - Supplemental Instructions

Table of Contents

Advertisement

S
dc: p
mart
1. Turn OFF AC power.
2. Connect photo eye wiring.
NOTE: Run a jumper between photo eye -24V and CM terminals.
3. Turn ON power.
NOTE: Make sure both AC & DC switches are ON and the red battery
wire is plugged in.
4. Access the Installer Menu. Configure SENSOR
setting accordingly. For example, Eye Close,
Eye Open, or Eye Both.
CAUTION
All external entrapment protection sensors must be NC sensor
outputs and wired to the SENSOR COM terminal for monitoring
and powering purposes. The sensor becomes actively powered
when the gate operator receives a run command.
Reflecti-GUARD Photo Eye
COMMON / NEG. to SENSOR COM
+24V
www.hysecurity.com © 2016
e
/ r
Hoto
ye
Connect NC relay
wire to SENSOR 1,
2, or 3.
Jumper, PWR -24V to
relay CM
-G
efLectI
uard
COM
COM
COM
COM
COM
COM
COM
COM
STOP
OPEN
CLOSE
OPEN
P ARTIAL
11
SENSOR 2
OPEN
EYE
10
SENSOR 3
EXIT
EXIT
LOOP
LOOP
BLOCK
EXIT
EXIT
IN OBS
LOOP
LOOP
OUT OBS
LOOP
LOOP
CENTER
LOOP
LOOP
EDGE
SENSOR 1
EYE
SENSOR
COM
COM
+ 24 V
EMERG
OPEN
SHOW
LEDs
NOTE: If you receive an Alert, "!ACTION BLOCKED"
"Photo Eye Open" PEO or "Photo Eye Close" PEC, take
steps to align the photo eye. Refer to Photo Eye
Alignment on page 12.
Quick Start
(rG-r)
Installer Menu Settings
S2 0
SENSOR #2 TYPE
CLOSE
MENU
OPEN
STOP
S2 2 (EYE CLOSE)
SELECT
PREV
NEXT
SENSOR #2 TYPE
CLOSE
OPEN
STOP
SELECT
PREV
NEXT
9
8
7
6
5
4
3
2
1
D0726 Rev. J
RESET
MENU
RESET
41