(1) Conversion disable
7
7.3 Online Module Change Procedure
- 26
7.3.5 When user range setting is used and initial setting was made with sequence program (other system is
When user range setting is used and initial setting was made
with sequence program (other system is available)
(a) Take the following steps to disable the conversion:
1) Set D/A conversion enable/disable setting (Un\G0) to All channel conversion
disable (3F
).
H
2) Turn Operating condition setting request (Y9) from off to on to stop the conver-
sion.
3) Operating condition setting completed flag (X9) turns off from on.
4) Check that the conversion is stopped by seeing the actual analog output value.
5) Turn Operating condition setting request (Y9) from on to off.