SETUP AND PROCEDURES BEFORE OPERATION
4
- 11
4.5 Intelligent Function Module Switch Setting
(a) I/O assignment setting screen
Set the following for the slot in which the Q66DA-G is mounted.
The type setting is required; set other items as needed.
Type
:Select "intelli."
Model name
:Enter the module model name.
Points
:Select 16 points.
Start XY
:Enter the start I/O signal for the Q66DA-G.
Detailed setting :
1) When using in the standard system configuration (on the main or extension
base), specify the control CPU of the Q66DA-G.
The analog output status of when an error has occurred in the Q66DA-G is
determined according to the setting of "HOLD/CLEAR function setting" of the
switch setting for intelligent function module. Therefore, the setting of "Error
time output mode" is invalid.
2) When using on a remote I/O station, if the analog output is to be held in the
case of a link error, "Error time output mode" must be set to "Hold".
3) Switch setting for intelligent function module dialog box
Click on [Switch setting] on the I/O assignment setting dialog box to display the
dialog box shown below, then set switches 1 to 5.
The switches can easily be set if values are entered in hexadecimal. Change
the entry format to hexadecimal and then enter the values.