Mitsubishi Electric Q66DA-G User Manual page 104

Channel isolated digital-analog converter module
Hide thumbs Also See for Q66DA-G:
Table of Contents

Advertisement

5
UTILITY PACKAGE (GX Configurator-DA)
(3) User range restoration
5
- 28
5.6 Monitoring/Test
5.6.4 Pass data
(a) Set the user range to be used in the Setting value field of CH
cation setting, and click the
When the user range setting is completed, the set user range is displayed in the
current value field of CH
(b) Set the recorded values in the Setting value fields of CH
tings offset/gain values/user range settings offset/gain values.
(c) Select all the Setting value fields of CH
values/user range settings offset/gain values, and click the
When writing is completed, the set values are displayed in the Current value fields
of CH
Industrial shipment settings offset/gain values/CH
offset/gain values.
(d) Change the Setting value field of Pass data write request to "Request", and click
the
Make sure that the indication in the Current value field of Pass data write request
changes from "Request" to "OFF" on completion of writing.
Pass data classification setting.
Industrial shipment settings offset/gain
button.
Pass data classifi-
button.
Industrial shipment set-
User range settings
button.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents