3
SPECIFICATIONS
The following conditions should be satisfied when the analog output HOLD/
CLEAR function is used on a MELSECNET/H remote I/O station.
• The master module of function version D or later and the remote I/O mod-
ule of function version D or later are required.
• Validate the station unit block guarantee of the send side cyclic data.
• The setting for holding the Q66DA-G output in the case of a link error
must be made in the "Error time output mode in the I/O assignment set-
ting". (Refer to Section4.5 (2).) The HOLD/CLEAR setting by the intelli-
gent function module switch is invalid. This setting is validated on a per-
module basis, and is not made on a per-channel basis. Therefore, to
make the output status at a stop error or STOP of the programmable con-
troller CPU matched with the output status at a link error, set the same.
HOLD/CLEAR setting to all channels. (Refer to the table below.)
Hold analog output
Clear analog output
(Output offset value)
For the station unit block guarantee of the cyclic data, refer to the Q Correspond-
ing MELSECNET/H Network System Reference Manual (Remote I/O Network).
Error time output mode
Hold
Clear
3.2 Function List
3.2.1 Analog output HOLD/CLEAR function
HOLD/CLEAR setting
(Same setting to all channels)
HOLD
CLEAR
3
- 10
1
2
3
4
5
6
7
8