Mitsubishi Electric Q66DA-G User Manual page 94

Channel isolated digital-analog converter module
Hide thumbs Also See for Q66DA-G:
Table of Contents

Advertisement

5
UTILITY PACKAGE (GX Configurator-DA)
[Explanation of items]
(1) Items
5
- 18
5.5 Auto Refresh Setting
Module side Buffer size
Module side Transfer word count : Displays the number of words to be transferred
Transfer direction
PLC side Device
: Displays the buffer memory size of the setting
item (fixed at one word).
to the CPU devices from the designated
address (fixed at one word).
: " " indicates that data are written from the
device to the buffer memory.
" " indicates that data are loaded from the
buffer memory to the device.
: Enter a CPU module side device that is to be
automatically refreshed.
Applicable devices are X, Y, M, L, B, T, C, ST, D,
W, R, and ZR.
When using bit devices X, Y, M, L or B, set a
number that can be divided by 16 points (exam-
ples: X10, Y120, M16, etc.)
Also, buffer memory data are stored in a 16-
point area, starting from the specified device
number.
For example, if X10 is entered, data are stored
in X10 to X1F.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents