Installation Requirements
Grounding Requirements
NOTE
3–12
iSTAR eX Installation and Configuration Guide
Grounding requirements are as follows:
Use 3-conductor minimum 18 gauge AC ground wire
Ensure that the iSTAR eX controller is properly connected to an earth
ground at the ground stud near the AC input wiring.
Ensure that the shield wire is grounded to the nearest earth/ground
connection at one end only of the cable.
Disconnect the ground wire last to provide maximum protection to the
equipment and personnel.
For grounding information, see the section "Grounding Procedure" on
page
4-13.
All cabling must be shielded.